OUTPUT |
|
Output Volt Amp Capacity (VA) | 10000 |
Output kVA capacity (kVA) | 10 |
Output Watt Capacity (watts) | 9000 |
Output kW capacity | 9.0 |
Output power factor | 0.9 |
Output Capacity Details | Supports up to 105% load continuously in double conversion mode, 106 to 125% for 1 minute, 126% to 150% for 30 seconds; Loads over 150% trigger immediate bypass mode operation to support loads directly from mains power; Double conversion mode is automatically restored as load levels are reduced to 95% or less |
Nominal Output Voltage(s) Supported | 200V; 208V; 220V; 230V; 240V |
Nominal Voltage details | Voltage selection via front panel LCD interface |
Frequency compatibility | 50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion |
Frequency compatibility details | Output frequency matches input nominal on startup; Frequency conversion mode enables conversion of 60Hz to 50Hz or 50Hz to 60Hz (no de-rating) |
Output voltage regulation (line mode) | +/- 2% |
Output voltage regulation (Economy line mode) | +/- 10% |
Output voltage regulation (Battery mode) | +/- 2% |
Built-in UPS output receptacles | Hardwire |
Output AC waveform (AC mode) | Pure Sine wave |
Output AC waveform (battery mode) | Pure Sine wave |
INPUT |
|
Rated input current (at maximum load) | 56.1A (200V), 54A (208V), 51A (220V), 48.8A (230V), 46.8A (240V) |
Nominal Input Voltage(s) Supported | 200V AC; 208V AC; 220V AC; 230V AC; 240V AC |
UPS input connection type | Hardwire |
UPS input connection description | 3 wire single phase input (L1, L2, G) |
Recommended Electrical Service | 60A |
Phase | Single-Phase |
BATTERY |
|
Full load runtime (minutes) | 4.3 min. (9000w) |
Half load runtime (minutes) | 12.5 min. (4500w) |
Expandable battery runtime | Supports extended runtime with optional external battery packs |
External battery pack compatibility | BP240V10RT3U; BP240V557C-1PH; BP240V787C-1PH; BP240V1037C-1PH; BP240V1407C-1PH |
DC system voltage (VDC) | 240 |
Battery recharge rate (included batteries) | Less than 8 hours from 10% to 90% |
Battery replacement description | Hot-swappable, user replaceable external battery packs |
VOLTAGE REGULATION |
|
Voltage regulation description | 2% output voltage regulation in standard online, double-conversion mode |
Overvoltage correction | Corrects overvoltages up to 300V |
Undervoltage correction | Corrects undervoltages as low as 100V |
LEDS ALARMS & SWITCHES |
|
LED Indicators | 6 LEDs indicate line power, online mode, economy/bypass mode, on-battery, charger and AC output status; LCD screen offers additional information and control options |
Front panel LCD display | Selectable LCD display with scroll and selection buttons enables UPS control and detailed monitoring options; LED/LCD panel rotates for viewing in rack/tower formats; LCD Display supports ENGLISH, FRENCH, GERMAN, ITALIAN, SPANISH and PORTUGUESE (see manual) |
Alarms | Unique audible alarms for all major UPS, environmental and power conditions (see manual) |
Alarm cancel operation | Alarm cancel switch |
Switches | 2 Switches control off/on power status and alarm-cancel/self-test operation; 2 additional switches support set and execute scrolling LCD functions; bundled PDU includes bypass switch to enable hot-swap UPS power module replacement |
SURGE / NOISE SUPPRESSION |
|
UPS AC suppression response time | Instantaneous |
EMI / RFI AC noise suppression | Yes |
PHYSICAL |
|
Installation form factors supported with included accessories | Tower |
Included mounting accessory description | 2 sets of adjustable 4 post rack rails included; 2-9USTAND tower kit included |
Installation form factors supported with optional accessories | 2 post rackmount (2POSTRMKITHD) |
Optional mounting accessory notes | 2 sets of 2POSTRMKITHD required for 2 post rackmount installation |
Primary form factor | Rackmount |
UPS / Power Module dimensions in primary form factor (height x width x depth / inches) | 5.14 x 17.5 x 25.82 |
UPS / Power Module dimensions in primary form factor (height x width x depth / cm) | 13.1 x 44.4 x 65.6 |
Installed whole system maximum rack depth (inches) | 32.5 |
Installed whole system maximum rack depth (cm) | 82.6 |
Rack Height | 6U |
Secondary form factor | Tower |
UPS / Power Module weight (lbs) | 43 |
UPS / Power Module weight (kg) | 19.5 |
Included battery pack dimensions (height x width x depth / inches) | 5.25 x 17.5 x 25 |
Included battery pack dimensions (height x width x depth / cm) | 13.3 x 44.4 x 63.5 |
Included battery pack weight (lbs) | 158.7 |
Included battery pack weight (kg) | 72 |
UPS Shipping dimensions (height x width x depth / inches) | 38.25 x 31.5 x 23 |
UPS Shipping dimensions (height x width x depth / cm) | 97.2 x 80 x 58.4 |
Shipping weight (lbs) | 327.6 |
Shipping weight (kg) | 148.7 |
Cooling method | Fan |
UPS housing material | Steel |
ENVIRONMENTAL |
|
Operating Temperature Range | +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius |
Storage Temperature Range | +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius |
Relative Humidity | 0 to 95%, non-condensing |
AC mode BTU / hr. (full load) | 3415 |
AC economy mode BTU / hr. (full load) | 1275 |
AC economy mode efficiency rating (100% load) | 96% |
Operating Elevation (ft.) | 0-3000m (0 to 10,000 ft.) |
Audible Noise | 60 dBA at front side 1 meter |
Operating Elevation (m) | 0-3000 m |
COMMUNICATIONS |
|
Communications interface | USB (HID enabled); DB9 Serial; EPO (emergency power off); Slot for SNMP/Web interface |
Network monitoring port description | Additional contact closure support with optional RELAYIOCARD and RELAYIOMINI interface cards. RELAYIOMINI installation requires removal of panel containing USB ports |
PowerAlert software | Included |
Communications cable | USB, DB9 serial and EPO cables included |
WatchDog compatibility | Supports Watchdog application, OS and hard-reboot restart options for remote applications |
LINE / BATTERY TRANSFER |
|
Transfer time | No transfer time (0 ms.) in online, double-conversion mode |
Transfer time (economy mode) | 8 ms. typical power failure response in optional economy mode |
Low voltage transfer to battery power (setpoint) | 100V |
High voltage transfer to battery power (setpoint) | 300V |
SPECIAL FEATURES |
|
Cold Start (startup in battery mode during a power failure) | Cold-start operation supported |
Economy mode operation | Optional economy mode enables high efficiency bypass operation with a maximum output voltage variation of +/-10%. Double conversion mode is automatically restored as mains voltage varies beyond +/-10% with less than 1 millisecond transfer time between modes. |
High availability UPS features | Automatic inverter bypass; Manual bypass switch; Detachable hot-swap PDU; Hot swappable UPS power module; Hot swappable batteries |
Green & high efficiency features | High efficiency economy mode operation; Schedulable daily hours of economy mode operation |
CERTIFICATIONS |
|
UPS Certifications | Tested to UL1778 (USA); Tested to CSA (Canada); Tested to NOM (Mexico); CE; Meets FCC Part 15 Category A (EMI) |
UPS Certification details | IEC 61000-4-5 1995 B Surge Immunity |
0
Shopping cart
Tsh 0
- Your cart is empty
- Continue Shopping