Technical Description
- Battery Configuration: 16 × 9Ah 12V sealed lead-acid maintenance-free batteries
- Total Capacity: 1728VAh (144V nominal × 9Ah)
- Form Factor: Standard 19″ rackmount with 2U height profile.
- Dimensions: Approximately 89mm (H) × 438mm (W) × 630mm (D)
- Weight: Approximately 55-60kg fully loaded.
- Connection Interface: Anderson Powerpole or proprietary connector compatible with Pro Series UPS.
- Charge Profile: Float charge voltage 163.2V DC (2.27V per cell)
- Operating Temperature: 0°C to 40°C (32°F to 104°F)
- Expected Battery Life: 3-5 years at 25°C ambient temperature.
- Hot-Swappable: Designed for battery replacement without powering down connected UPS
- Overcharge Protection: Built-in circuit protection prevents damage from charging anomalies.