MODEL: EP-UPS1000UC13OR
Capacity (VA / Watts): 1,000 VA / 1,000 W
Phase: Single phase with ground
INPUT
Nominal Voltage 200 / 208 / 220 / 230 / 240 Vac
Operating Voltage Range
Low voltage of transferring to bypass:
160 Vac ± 5 % @ 100 % – 80 % load, 120 Vac ± 5 % @ 70 % – 60 % load,
110 Vac ± 5 % @ 60 % – 50 % load (Ambient temp. < 35 °C)
Low threshold voltage of recovering from bypass:
175 Vac ± 5 % @ 100 % – 80 % load, 135 Vac ± 5 % @ 70 % – 60 % load,
125 Vac ± 5 % @ 60 % – 50 % load (Ambient temp. < 35 °C)
High voltage of transferring to bypass :300 Vac ± 5 %
High threshold voltage of recovering from bypass: 290 Vac ± 5 %
Input Voltage Range: 55 – 150 Vac or 110 – 300 Vac @ 60 % load, 80 – 145 Vac or 160 – 300 Vac @ 100 % load
Operating frequency range: 40 – 70 Hz
Power Factor: 0.99
Generator input: Supported
OUTPUT
Output Voltage: 200 / 208 / 220 / 230 / 240 Vac
Power Factor: 1
Voltage regulation: ± 1 %
Frequency Line mode (synchronized range): 47 – 53 Hz or 57 – 63 Hz
Frequency Bat. mode: 50 / 60 Hz ±1 Hz
Crest Factor 3:1
Harmonic Distortion (THDv): ≤ 2 % THD (Linear load)
≤ 4 % THD (Non-linear load)
Waveform: Pure Sinewave
Transfer time: AC mode <-> batt. mode -Zero
Inverter <-> bypass- 4 ms (Typical)
EFFICIENCY
AC Mode: 88 % 92 % 92 %
Battery mode: 85 % 88 % 90 %
BATTERY
Battery type: 12 V, 9 Ah
Number of batteries: 2
Typical recharge time: 4 hours charge to 90 % capacity
Charging voltage: 27.4 Vdc ± 1 % 54.7 Vdc ± 1 % 82.1 Vdc ± 1 %
Charging current (max): 1 A or 2 A
SYSTEM FEATURES
AC mode: Ambient temp. < 35 °C –
105 % – 110 %: UPS will transfer to bypass mode within 10 min of return of utility power
110 % – 130 %: UPS will transfer to bypass mode within 1 min of return of utility power
130 % – 150 %: UPS will transfer to bypass mode within 5 sec of return of utility power
> 150 %: UPS will transfer to bypass mode immediately upon return of utility power
Battery mode: 35 °C < ambient temp. < 40 °C
105 % – 110 %: UPS will transfer to bypass mode within 1 min of return of utility power
110 % – 130 %: UPS will transfer to bypass mode within 5 sec of return of utility power
> 130 %: UPS will transfer to bypass mode immediately upon return of utility power
Short circuit: Hold whole system
Overheat Line mode: Switch to bypass. Backup mode: UPS will shut down immediately
Battery low: Alarm and switch off
EPO (optional): Shut down UPS immediately
Audible & visual alarms: Line failure, battery low, over load, system fault
MANAGEMENT
Communication ports: USB, RS232, SNMP card (optional), Relay card (optional)
OPERATING ENVIRONMENT
Operating temperature: 0 – 40 °C
Storage temperature: -25 °C – 55 °C
Humidity range: 20 – 90 % RH @ 0 – 40 °C (Non-condensing)
Recommended altitude: < 1500 m
Noise level: Less than 50 dBA at 1 m
PHYSICAL FEATURES
Dimensions (W * D * H): 440mm * 325 mm* 86.5
Approx. net weight (kg): 11.3
0
Shopping cart
Tsh 0
- Your cart is empty
- Continue Shopping