Technical Specification
- Capacity: 40kVA / 40kW at unity power factor (1.0) for maximum real power output.
- Input: Three-phase 400V (340-477V operating range), 50/60Hz ±5Hz frequency.
- Output: Three-phase 400V (adjustable 380/400/415V), <1.5% voltage distortion with linear loads.
- Efficiency: Up to 96% in normal operation and up to 99% in ECO mode.
- Communication: Built-in SNMP card with Ethernet port for remote monitoring.
- Protection: Input/output circuit breakers and advanced overload protection capabilities.
- Battery Type: Compatible with VRLA maintenance-free batteries (internal and external options)
- Runtime: Configurable with additional battery modules for extended backup times.
- Display: Multi-function LCD display with mimic diagram and status indicators.
- Dimensions: 530 x 772 x 1143 mm (W x D x H) with compact footprint for space-constrained environments.